The lead level for one faucet (special education room, fix reference #16) have exceeded the provincial drinking water standard of 10 ug/L (micrograms per litre).

Fixture Number: FRA-10
Test date: June 12, 2018
Standing result: 4.5 ug/L
Flushed result: 77.9 ug/L
Corrective action:

  • Permanently render fixture FRA-10 unusable for drinking (bagged it);
  • Replace old drinking water fixture and sample the new one.