The lead level for faucet – fixture number COR-13 (hall room 2, fix reference # 37) and bottle filler – fixture number COR-19 (corridor by room 16, fix reference # 806) have exceeded the provincial drinking water standard of 10 ug/L (micrograms per litre).

Fixture Number: COR-13
Test date: May 31, 2018
Standing result: 4.9 ug/L
Flushed result: 11.9 ug/L

Fixture Number: COR-19
Test date: June 1, 2018
Standing result: 11.0 ug/L
Flushed result: 3.7 ug/L

Corrective action:

  • Flush ALL drinking water fixtures daily
  • Permanently render fixture COR-13 unusable for drinking (is for handwashing only)