Water testing results showed that two fixtures were impacted:

Fixture Number: PRE-09; drinking fountain (change room FR#130)
Test date: August 28, 2019
Standing result: 21.3 ug/L
Flushed result: <1.0 ug/L

Fixture Number: PRE-10; drinking fountain (change room FR#134)
Test date: August 28, 2019
Standing result: 10.8 ug/L
Flushed result: <1.0 ug/L

Corrective actions:

  • Flush impacted fixtures daily for the next 24 months